# On-site poller
`refusol_poller.py` (lives on the site laptop, not in this repo) reads the inverters over USS/TCP
(port 21062, USS address 0). It sends each cycle to the backend through
`backend_client.py` — copy that file next to the poller.
## Wiring it into `refusol_poller.py`
At the top of the file:
```python
from backend_client import BackendClient
BACKEND_URL = "https://solar.bonamin.net"
API_KEY = "same value as API_KEY in the server's .env"
backend = BackendClient(BACKEND_URL, API_KEY)
```
At the end of every poll cycle, one dict per inverter that answered:
```python
readings = []
for inverter_id, values in polled.items(): # however the poller holds them
readings.append({"inverter_id": inverter_id, **values})
backend.send(readings) # also call it when the list is empty
```
Each dict uses the keys below (all optional — send what was read). Anything
else you include (e.g. a newly discovered parameter as `"p0xx_raw": 1234`) is
stored too and shows under "Other (unmapped)" on the inverter page.
State of the map as verified on site (2026-10-21):
| key | unit | status | source |
|---|---|---|---|
| `ac_power_total_w` | W | ✅ sent | **Computed** by the poller: Σ (phase V × phase I), forced to 0 when the inverter isn't feeding. *Not* P06D — P06D sits latched at 21450 on any feeding unit (nameplate/limit, not live power). |
| `ac_voltage_l1_v` / `_l2_v` / `_l3_v` | V | ✅ sent | P050 / P05B / P064 raw / 40 |
| `ac_current_l1_a` / `_l2_a` / `_l3_a` | A | ✅ sent | P068 / P069 / P06A raw / 100 |
| `grid_frequency_hz` | Hz | ✅ sent | P06C raw / 20 |
| `temperature_c` | °C | ✅ sent | P070 raw >> 16 |
| `status_code` | – | ✅ sent | PZD status word. **7 and 8 = feeding** (7 on INV1's OEM board, 8 on the standard units); anything else shows as Standby. Other values not decoded yet. |
| `status_text` | – | ✅ sent | `"feeding"` / `"standby/not feeding"` |
| `dc_voltage_mppt1_v` / `_mppt2_v` | V | ❌ not sent | P052 / P054 are static nameplate/limit values, not live. Real registers TBD. |
| `dc_current_mppt1_a` / `_mppt2_a` | A | ❌ not sent | P05A / P05C likewise static. Real registers TBD. |
| `daily_energy_wh` | Wh | ❌ not sent | P063 IND=0 is frozen, not accumulating. Real register TBD. Until then the backend **estimates** daily energy by integrating `ac_power_total_w` (shown with ≈). |
| `total_energy_wh` | Wh | ❌ not sent | P063 IND=11 decode wrong. Real register TBD. Lifetime shows "not available yet". |
| `error_code` | – | ❌ not sent | No fault register confirmed yet. Absent = no fault. Non-zero will show the inverter as **Fault**. |
Unmapped diagnostics currently sent (stored, shown under "Other (unmapped)",
never treated as telemetry): `p06d_raw_latched`, `p052_static_v`,
`p05a_static_a`, `p063_ind0_raw`.
Inverter IDs (permanent database keys): INV1 = 192.168.1.11, INV2 =
192.168.1.12, INV3 = 192.168.1.13 (reserved, not connected yet), INV4 =
192.168.1.221, INV5 = REFUsol 20K-3T (reserved, no read path yet). An
inverter appears on the dashboard the first time it reports.
**Timestamps must be UTC.** Send them with the right offset (e.g.
`datetime.now(timezone.utc).isoformat()`), or leave `timestamp` out and let
`backend_client.py` add it. A reading stamped more than 5 min in the future
(e.g. local Athens time labelled `+00:00`) is stored at the time it was
received instead, and the response's `clamped_future` count says so.
`send()` stamps each reading with the current UTC time, buffers to
`unsent_readings.jsonl` when the internet is down and re-sends later, and
never raises — a backend problem can't stop the polling loop.
**Call `send([])` even when no inverter answered.** That's the heartbeat that
lets the dashboard say "inverter not responding" (site online) instead of
"datalogger offline" (site/internet down).