P06D is a latched 21450 (not power), P052/P05A static, P063 frozen; power is computed V*I. Lists what's sent, what isn't, the unmapped diagnostics, the INV1-INV5 IP assignments, and that timestamps must be real UTC. The simulator now sends the same payload shape. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
On-site poller
refusol_poller.py (lives on the site laptop, not in this repo) reads the inverters over USS/TCP
(port 21062, USS address 0). It sends each cycle to the backend through
backend_client.py — copy that file next to the poller.
Wiring it into refusol_poller.py
At the top of the file:
from backend_client import BackendClient
BACKEND_URL = "https://solar.bonamin.net"
API_KEY = "same value as API_KEY in the server's .env"
backend = BackendClient(BACKEND_URL, API_KEY)
At the end of every poll cycle, one dict per inverter that answered:
readings = []
for inverter_id, values in polled.items(): # however the poller holds them
readings.append({"inverter_id": inverter_id, **values})
backend.send(readings) # also call it when the list is empty
Each dict uses the keys below (all optional — send what was read). Anything
else you include (e.g. a newly discovered parameter as "p0xx_raw": 1234) is
stored too and shows under "Other (unmapped)" on the inverter page.
State of the map as verified on site (2026-10-21):
| key | unit | status | source |
|---|---|---|---|
ac_power_total_w |
W | ✅ sent | Computed by the poller: Σ (phase V × phase I), forced to 0 when the inverter isn't feeding. Not P06D — P06D sits latched at 21450 on any feeding unit (nameplate/limit, not live power). |
ac_voltage_l1_v / _l2_v / _l3_v |
V | ✅ sent | P050 / P05B / P064 raw / 40 |
ac_current_l1_a / _l2_a / _l3_a |
A | ✅ sent | P068 / P069 / P06A raw / 100 |
grid_frequency_hz |
Hz | ✅ sent | P06C raw / 20 |
temperature_c |
°C | ✅ sent | P070 raw >> 16 |
status_code |
– | ✅ sent | PZD status word. 7 and 8 = feeding (7 on INV1's OEM board, 8 on the standard units); anything else shows as Standby. Other values not decoded yet. |
status_text |
– | ✅ sent | "feeding" / "standby/not feeding" |
dc_voltage_mppt1_v / _mppt2_v |
V | ❌ not sent | P052 / P054 are static nameplate/limit values, not live. Real registers TBD. |
dc_current_mppt1_a / _mppt2_a |
A | ❌ not sent | P05A / P05C likewise static. Real registers TBD. |
daily_energy_wh |
Wh | ❌ not sent | P063 IND=0 is frozen, not accumulating. Real register TBD. Until then the backend estimates daily energy by integrating ac_power_total_w (shown with ≈). |
total_energy_wh |
Wh | ❌ not sent | P063 IND=11 decode wrong. Real register TBD. Lifetime shows "not available yet". |
error_code |
– | ❌ not sent | No fault register confirmed yet. Absent = no fault. Non-zero will show the inverter as Fault. |
Unmapped diagnostics currently sent (stored, shown under "Other (unmapped)",
never treated as telemetry): p06d_raw_latched, p052_static_v,
p05a_static_a, p063_ind0_raw.
Inverter IDs (permanent database keys): INV1 = 192.168.1.11, INV2 = 192.168.1.12, INV3 = 192.168.1.13 (reserved, not connected yet), INV4 = 192.168.1.221, INV5 = REFUsol 20K-3T (reserved, no read path yet). An inverter appears on the dashboard the first time it reports.
Timestamps must be UTC. Send them with the right offset (e.g.
datetime.now(timezone.utc).isoformat()), or leave timestamp out and let
backend_client.py add it. A reading stamped more than 5 min in the future
(e.g. local Athens time labelled +00:00) is stored at the time it was
received instead, and the response's clamped_future count says so.
send() stamps each reading with the current UTC time, buffers to
unsent_readings.jsonl when the internet is down and re-sends later, and
never raises — a backend problem can't stop the polling loop.
Call send([]) even when no inverter answered. That's the heartbeat that
lets the dashboard say "inverter not responding" (site online) instead of
"datalogger offline" (site/internet down).
Trying the dashboard without the site
python fake_poller.py --url http://localhost:8090 --key change-me --backfill-days 30