From 42c7d182079990534fff36fbf5a4db94905578cc Mon Sep 17 00:00:00 2001 From: bonamin Date: Wed, 21 Oct 2026 09:43:56 +0300 Subject: [PATCH] docs: record the verified register map and inverter IDs P06D is a latched 21450 (not power), P052/P05A static, P063 frozen; power is computed V*I. Lists what's sent, what isn't, the unmapped diagnostics, the INV1-INV5 IP assignments, and that timestamps must be real UTC. The simulator now sends the same payload shape. Co-Authored-By: Claude Opus 5.5 --- README.md | 18 ++++++++++- poller/ONSITE_AGENT_BRIEF.md | 9 +++--- poller/README.md | 47 ++++++++++++++++++--------- poller/fake_poller.py | 61 +++++++++++++++--------------------- 4 files changed, 80 insertions(+), 55 deletions(-) diff --git a/README.md b/README.md index 202d213..60dd931 100644 --- a/README.md +++ b/README.md @@ -88,13 +88,29 @@ the chart picker without further changes. datalogger is still posting and the sun is up. At night that's **Sleeping**; if the datalogger itself is silent the state is **No data** (and a banner says so). -- **Fault** — the reading carries a non-zero `error_code`. +- **Fault** — the reading carries a non-zero `error_code`. No `error_code` + (the poller doesn't send one yet) means no fault. +- **Feeding / Standby** — online and `status_code` is in + `FEEDING_STATUS_CODES` (7, 8) → Feeding; any other code → Standby. An + inverter in standby while its peers produce is caught by the + underperformance check below. - **Check needed** — output below `UNDERPERFORM_RATIO` (75%) of the fleet median over the last 10 min (per kWp once every inverter has its array size set), or one MPPT input below half of the other. Thresholds are in `.env`. +### Energy + +Daily energy uses, in order: the inverter's daily counter +(`daily_energy_wh`), the growth of its lifetime counter, or — while neither +is decoded, which is the case today — AC power integrated over time +(trapezoid between consecutive readings, gaps over 5 min not bridged). The +estimate is flagged (`estimated: true` in the API, "≈" on the dashboard). +Lifetime energy shows "not available yet" until `total_energy_wh` is sent. + +The current state of the register map is in `poller/README.md`. + ## Data retention Raw readings older than `RETENTION_DAYS` (730) are purged every 6 h. The diff --git a/poller/ONSITE_AGENT_BRIEF.md b/poller/ONSITE_AGENT_BRIEF.md index 1be2f7f..93e4a47 100644 --- a/poller/ONSITE_AGENT_BRIEF.md +++ b/poller/ONSITE_AGENT_BRIEF.md @@ -11,7 +11,8 @@ the on-site side: read the inverters, POST the values. use it to send. It's standard library only. It timestamps readings, keeps them in `unsent_readings.jsonl` when the internet is down, re-sends them later, and never raises. -- `README.md` (next to this brief): the field names, units and scalings. +- `README.md` (next to this brief): the field names, units and the current + state of the register map (what's verified, what isn't sent yet). ## What to do every 60 s @@ -44,9 +45,9 @@ while True: e.g. `INV1`..`INV5` matching labels on the units. It's the database key. Pretty names are set later in the dashboard, not here. Allowed characters: letters, digits, `_ . -`. -3. **Send converted values**, not raw ones, using the keys and scalings in - `README.md` (e.g. `ac_voltage_l1_v` = P050 raw / 40). Leave out anything - you couldn't read; every field is optional. +3. **Send converted values**, not raw ones, using the keys in `README.md`. + Leave out anything you couldn't read or haven't verified; every field is + optional. Timestamps must be real UTC (see README). 4. **New or unconfirmed parameters:** send them too, under a descriptive key (e.g. `p0xx_raw`). The backend stores unknown keys and shows them on the inverter page under "Other (unmapped)". Tell the owner when a mapping is diff --git a/poller/README.md b/poller/README.md index 642bcfe..493b01c 100644 --- a/poller/README.md +++ b/poller/README.md @@ -1,6 +1,6 @@ # On-site poller -`refusol_poller.py` (not in this repo yet) reads the inverters over USS/TCP +`refusol_poller.py` (lives on the site laptop, not in this repo) reads the inverters over USS/TCP (port 21062, USS address 0). It sends each cycle to the backend through `backend_client.py` — copy that file next to the poller. @@ -30,20 +30,37 @@ Each dict uses the keys below (all optional — send what was read). Anything else you include (e.g. a newly discovered parameter as `"p0xx_raw": 1234`) is stored too and shows under "Other (unmapped)" on the inverter page. -| key | unit | source | -|---|---|---| -| `ac_voltage_l1_v` / `_l2_v` / `_l3_v` | V | P050 / P05B / P064 raw / 40 | -| `dc_voltage_mppt1_v` / `_mppt2_v` | V | P052 / P054 raw / 40 | -| `dc_current_mppt1_a` / `_mppt2_a` | A | P05A / P05C raw / 10 | -| `ac_current_l1_a` / `_l2_a` / `_l3_a` | A | P068 / P069 / P06A raw / 100 | -| `ac_power_total_w` | W | P06D raw | -| `grid_frequency_hz` | Hz | P06C raw / 20 | -| `temperature_c` | °C | P070 raw >> 16 | -| `daily_energy_wh` | Wh | P063 IND=0 raw × 10 | -| `total_energy_wh` | Wh | P063 IND=11 raw | -| `status_code` | – | inverter state, once identified | -| `error_code` | – | non-zero = fault (shows the inverter as **Fault**) | -| `status_text` | – | optional human text for the code | +State of the map as verified on site (2026-10-21): + +| key | unit | status | source | +|---|---|---|---| +| `ac_power_total_w` | W | ✅ sent | **Computed** by the poller: Σ (phase V × phase I), forced to 0 when the inverter isn't feeding. *Not* P06D — P06D sits latched at 21450 on any feeding unit (nameplate/limit, not live power). | +| `ac_voltage_l1_v` / `_l2_v` / `_l3_v` | V | ✅ sent | P050 / P05B / P064 raw / 40 | +| `ac_current_l1_a` / `_l2_a` / `_l3_a` | A | ✅ sent | P068 / P069 / P06A raw / 100 | +| `grid_frequency_hz` | Hz | ✅ sent | P06C raw / 20 | +| `temperature_c` | °C | ✅ sent | P070 raw >> 16 | +| `status_code` | – | ✅ sent | PZD status word. **7 and 8 = feeding** (7 on INV1's OEM board, 8 on the standard units); anything else shows as Standby. Other values not decoded yet. | +| `status_text` | – | ✅ sent | `"feeding"` / `"standby/not feeding"` | +| `dc_voltage_mppt1_v` / `_mppt2_v` | V | ❌ not sent | P052 / P054 are static nameplate/limit values, not live. Real registers TBD. | +| `dc_current_mppt1_a` / `_mppt2_a` | A | ❌ not sent | P05A / P05C likewise static. Real registers TBD. | +| `daily_energy_wh` | Wh | ❌ not sent | P063 IND=0 is frozen, not accumulating. Real register TBD. Until then the backend **estimates** daily energy by integrating `ac_power_total_w` (shown with ≈). | +| `total_energy_wh` | Wh | ❌ not sent | P063 IND=11 decode wrong. Real register TBD. Lifetime shows "not available yet". | +| `error_code` | – | ❌ not sent | No fault register confirmed yet. Absent = no fault. Non-zero will show the inverter as **Fault**. | + +Unmapped diagnostics currently sent (stored, shown under "Other (unmapped)", +never treated as telemetry): `p06d_raw_latched`, `p052_static_v`, +`p05a_static_a`, `p063_ind0_raw`. + +Inverter IDs (permanent database keys): INV1 = 192.168.1.11, INV2 = +192.168.1.12, INV3 = 192.168.1.13 (reserved, not connected yet), INV4 = +192.168.1.221, INV5 = REFUsol 20K-3T (reserved, no read path yet). An +inverter appears on the dashboard the first time it reports. + +**Timestamps must be UTC.** Send them with the right offset (e.g. +`datetime.now(timezone.utc).isoformat()`), or leave `timestamp` out and let +`backend_client.py` add it. A reading stamped more than 5 min in the future +(e.g. local Athens time labelled `+00:00`) is stored at the time it was +received instead, and the response's `clamped_future` count says so. `send()` stamps each reading with the current UTC time, buffers to `unsent_readings.jsonl` when the internet is down and re-sends later, and diff --git a/poller/fake_poller.py b/poller/fake_poller.py index 0dd344b..8bdf725 100644 --- a/poller/fake_poller.py +++ b/poller/fake_poller.py @@ -2,9 +2,11 @@ python fake_poller.py --url http://localhost:8090 --key change-me --backfill-days 30 ---backfill-days first loads that many days of history (one reading per -5 minutes), then it posts live readings every --interval seconds. Inverter -INV3 runs with a dead MPPT2 string so the warnings show up. +Sends what the real poller sends today (AC side, temperature, status code, +unmapped diagnostics; no DC or energy counters). --backfill-days first loads +that many days of history (one reading per 5 minutes), then it posts live +readings every --interval seconds. INV4 runs at half output (as if a string +fuse had blown) so the warnings show up. """ import argparse @@ -15,7 +17,7 @@ from datetime import datetime, timedelta, timezone from backend_client import BackendClient -INVERTERS = ["INV1", "INV2", "INV3", "INV4", "INV5"] +INVERTERS = ["INV1", "INV2", "INV4"] PEAK_W = 18_000 @@ -26,40 +28,32 @@ def sun_factor(t: datetime) -> float: return max(0.0, math.sin(math.pi * x)) if 0 < x < 1 else 0.0 -def reading(inv: str, t: datetime, state: dict) -> dict | None: +def reading(inv: str, t: datetime) -> dict | None: f = sun_factor(t) * random.uniform(0.93, 1.0) if f <= 0.01: return None # inverter asleep at night, doesn't answer - dead_mppt2 = inv == "INV3" - p_dc1 = PEAK_W / 2 * f - p_dc2 = 0 if dead_mppt2 else PEAK_W / 2 * f - v1, v2 = 560 + 60 * f, 560 + 60 * f - ac = int((p_dc1 + p_dc2) * 0.97) - day = t.date() - if state.get((inv, "day")) != day: - state[(inv, "day")] = day - state[(inv, "daily")] = 0 - state[(inv, "daily")] += ac * state["step"] / 3600 - state[(inv, "total")] = state.get((inv, "total"), 40_000_000) + ac * state["step"] / 3600 - i_ac = ac / 3 / 230 + feeding = f > 0.03 + w = int(PEAK_W * f * (0.5 if inv == "INV4" else 1.0)) if feeding else 0 + volts = [round(random.uniform(229, 236), 2) for _ in range(3)] + amps = [round(w / 3 / v, 2) for v in volts] return { "inverter_id": inv, "timestamp": t.isoformat(timespec="seconds"), - "ac_voltage_l1_v": round(random.uniform(228, 236), 1), - "ac_voltage_l2_v": round(random.uniform(228, 236), 1), - "ac_voltage_l3_v": round(random.uniform(228, 236), 1), - "dc_voltage_mppt1_v": round(v1, 1), - "dc_voltage_mppt2_v": round(v2 if not dead_mppt2 else 30.0, 1), - "dc_current_mppt1_a": round(p_dc1 / v1, 1), - "dc_current_mppt2_a": round(p_dc2 / v2, 1), - "ac_current_l1_a": round(i_ac, 2), - "ac_current_l2_a": round(i_ac, 2), - "ac_current_l3_a": round(i_ac, 2), - "ac_power_total_w": ac, + "ac_voltage_l1_v": volts[0], + "ac_voltage_l2_v": volts[1], + "ac_voltage_l3_v": volts[2], + "ac_current_l1_a": amps[0], + "ac_current_l2_a": amps[1], + "ac_current_l3_a": amps[2], + "ac_power_total_w": w, "grid_frequency_hz": round(random.uniform(49.95, 50.05), 2), "temperature_c": int(30 + 25 * f), - "daily_energy_wh": int(state[(inv, "daily")] // 10 * 10), - "total_energy_wh": int(state[(inv, "total")]), + "status_code": (7 if inv == "INV1" else 8) if feeding else 3, + "status_text": "feeding" if feeding else "standby/not feeding", + "p06d_raw_latched": 21450, + "p052_static_v": 312.5, + "p05a_static_a": 45.0, + "p063_ind0_raw": 1872, } @@ -72,13 +66,11 @@ def main() -> None: args = ap.parse_args() client = BackendClient(args.url, args.key, spool_path="fake_unsent.jsonl") - state: dict = {} if args.backfill_days: - state["step"] = 300 t = datetime.now(timezone.utc) - timedelta(days=args.backfill_days) batch: list[dict] = [] while t < datetime.now(timezone.utc): - batch += [r for inv in INVERTERS if (r := reading(inv, t, state))] + batch += [r for inv in INVERTERS if (r := reading(inv, t))] if len(batch) >= 1000: client.send(batch) batch = [] @@ -86,10 +78,9 @@ def main() -> None: client.send(batch) print(f"Backfilled {args.backfill_days} days") - state["step"] = args.interval while True: now = datetime.now(timezone.utc) - batch = [r for inv in INVERTERS if (r := reading(inv, now, state))] + batch = [r for inv in INVERTERS if (r := reading(inv, now))] ok = client.send(batch) print(f"{now:%H:%M:%S} sent {len(batch)} readings, ok={ok}") time.sleep(args.interval)